Transformer Impedances

The tables below list the current transformer impedances for Detroit Edison's power distribution transformers. This information is necessary for calculating available fault current.

Single Phase Overhead Distribution Transformers
Dual Voltage 7.6kV X 4.8kV Primary Single Phase - 120/240
Size in kVA% Impedance
151.6 - 3.0
251.6 - 3.0
501.6 - 3.0
1001.6 - 3.0
1671.8 - 3.0
Dual Voltage 7.6kV X 4.8kV Primary Single Phase - 277 VOLT
Size in kVA% Impedance
501.6 - 3.0
1001.6 - 3.0
1671.8 - 3.0
Dual Voltage 7.6kV X 4.8kV Primary Single Phase - 120 VOLT
Size in kVA% Impedance
151.6 - 3.0
251.6 - 3.0
501.6 - 3.0
1001.6 - 3.0
1671.8 - 3.0
7.6 kV Primary Single Phase - 7620/13,200Y - 120/240 VOLTS
Size in kVA% Impedance
1001.6 - 3.0
2503.0 - 3.5
Isolation transformers 7620/13,200 - 4800/8320 VOLTS
Size in kVA% Impedance
751.6 - 3.0
2501.6 - 3.5
3331.6 - 3.7
5001.6 - 3.7

 

Pad Mounted, Dead Front, Single Phase, Distribution Transformers
13,200 Grd Y/7620 - 240/120 VOLTS
Size in kVAFuse Amps.% Impedance
25101.5 - 2.75
50151.5 - 2.5
100241.5 - 2.5
167281.8 - 3.0
250283.0 - 3.4

 

Pad Mounted, Dead Front, Single Phase, Distribution Transformers
Dual Voltage 4800/8320Y X 13,200 GrdY/7620 - 240/120 VOLTS
Size in kVAFuse Amps.% Impedance
50361.5 - 2.5
100591.5 - 2.5
167681.8 - 3.0

 

Pad Mounted, Dead Front, Three Phase, Distribution Transformers
13,200 GRD Y/7620 - 208/120 VOLTS
Size in kVAFuse Amps.% Impedance
15091.6 - 2.5
300151.6 - 2.5
500241.8 - 3.5
750285.75
13,200 GRD Y/7620 - 480/277 VOLTS
Size in kVAFuse Amps.% Impedance
15091.6 - 2.5
300151.6 - 2.5
500241.8 - 3.5
750285.75
4800 X 13,200 GRD Y/7620 - 208/120 VOLTS*
Size in kVAFuse Amps.% Impedance
75121.6 - 2.5
150241.6 - 2.5
300341.6 - 2.5
500481.8 - 3.5
*If connected on 13.2kV system use corresponding C fuse for kVA size.
4800 X 13,200 GRD Y/7620 - 240/120 VOLTS*
Size in kVAFuse Amps.% Impedance
300341.6 - 2.5
500481.8 - 3.5
*If connected on 13.2kV Y-Y system use corresponding C fuse for kVA size.
4800 X 13,200 GRD Y/7620 - 480/277 VOLTS*
Size in kVAFuse Amps.% Impedance
75121.6 - 2.5
150241.6 - 2.5
300341.6 - 2.5
500481.8 - 3.5
*If connected on 13.2kV Y-Y system use corresponding C fuse for kVA size.

 

Pad Mounted, Live Front, Three Phase, Distribution Transformers
4800 X 13,200 - 208/120 VOLTS
Size in kVA% Impedance
7505.75
10005.75
501.6 - 3.0
4800 X 13,200 - 480/277 VOLTS
Size in kVA% Impedance
7505.75
10005.75
15005.75

 